Zhechang Technology
Battery management System ZC-BMS02

1.Real-time monitoring the voltage of battery to avoid the measurement error for the long line.

2.High accuracy, low power, small size.

Description
Online Battery management System ZC-BMS02

1.Real-time monitoring the voltage of battery to avoid the measurement error for the long line. 2.High accuracy, low power, small size. 3.Based on the discreteness of battery pack's daily operation data, the capacity and health status of each battery were estimated by neural network algorithm. 4.USB/RS485/RJ45 communication interface which can communicate with the computer real-time data or control other intelligent devices. 5.Perfect software can real-time display each measurement data and curve, provide data query, report generation and other functions. 6.it have automatic wizard function, without too much manual intervention,it is simple to use .

Model
ZC-BMS02/ ZC-BMS12
Accuracy
Internal resistance consistency
±(2.5%+25μΩ)
Voltage detection accuracy
±0.2%
Current detection accuracy
±1%
Temperature detection accuracy
±0.5℃
SOC accuracy
±5%(For 2V Batteries)
±10%(For 12V Batteries)
Specification
Monitoring Range
A single module can support 20, 24, 27, 32, 54 batteries

Voltage detection range
1.5~3V(For 2V Batteries)/ ±0.2%
4.5~8V(For 6V Batteries)/±0.2%
8.0~15V(For 12V Batteries )/±0.2%
Measurement range of internal resistance
0.05mΩ~100mΩ
Current detection range
0~±2000A
Communication interface
Interface and Settings
RS485/CAN
Data Storage
Flash,64Mbit( Data export via USB)
Communication rate
4800.9600(Default).14400.19200bps
Electrical Specifications
Input insulation resistance
≥10MΩ 500V

The work environment
Environment Temp:-20~+65℃
Humidity:40%~95%
Environmental magnetic field: < 400A/m, no flammable and explosive gas is allowed around
Mechanical characteristics
Size(LxWxH)
19Incu 1U(482.6x264x43.7mm) 6V12V
19inch 1U(482.6x200mmx43.7mm) 2V
Installation method
rack or wall mount (install according to user's requirement)
Weight
About 3Kg
Function and Display
Battery maintenance mode
Automatic or remote manual control (configurable)
Display
LED working status indication
Alarm Mode
dry contact output, closed in case of failure
Control Mode
dry contact output, reserved
Power Demand
Power
AC/DC220V±15%,DC110V±15%,DC48V±15%

Contact

Feedback

TOP